TH150 400-150-000-C 5/9/06 3/6
4. Configuration
4.1 Configuration Menus
1A model
Application
(section 4.2)
Default mode &
Output 1 type
(section 4.3.1)
NSB value
(section 5.6)
Output 1
min. opening
(section 4.3.2)
Maximum
setpoint
(section 4.6)
Minimum
setpoint
(section 4.6)
0
Internal sensor
0 Cool / 0-10V 1 1°C (2°F) 0 0%
Can be set
between 35°C
(95°F) and
’’minimum
setpoint + 1’’
Default value
is 35°C (95°F)
Can be set
between 10°C
(50°F) and
’’maximum
setpoint - 1’’
Default value
is 10°C (50°F)
1 Room 1 Heat / 0-10 V 2 2°C (4°F) 1 10%
2 Return 2
Cool / 2-10 V 3 3°C (6°F) 2 20%
3 Supply 3 Heat / 2-10 V 4 4°C (8°F) 3 30%
4 Auto changeover 5 5°C (10°F) 4 40%
5 Limited cooling 6 6°C (12°F) 5 50%
7 7°C (14°F)
8 8°C (16°F)
9 9°C (18°F)
1F model
Application
(section 4.2)
Default mode
(section 4.3.1)
NSB value
(section 5.6)
Output 1
min. opening
(section 4.3.2)
Output 1
opening time
(section 4.3.3)
Maximum
setpoint
(section 4.6)
Minimum
setpoint
(section 4.6)
0
Internal sensor
0 Cool 1 1°C (2°F) 0 0% 080
Can be set
between 35°C
(95°F) and
’’minimum
setpoint + 1’’
Default value
is 35°C (95°F)
Can be set
between 10°C
(50°F) and
’’maximum
setpoint - 1’’
Default value
is 10°C (50°F)
1 Room 1 Heat 2 2°C (4°F) 1 10% 1 90
2 Return 3
3°C (6°F) 2 20% 2 100
3 Supply 4 4°C (8°F) 3 30% 3 110
4 Auto changeover 5 5°C (10°F) 4 40% 4 120
5 Limited cooling 6 6°C (12°F) 5 50% 5 130
7 7°C (14°F) 6 140
8 8°C (16°F) 7 150
9 9°C (18°F) 8 160
1A2T model
Application
(section 4.2)
Default mode &
Output 1 type
(section 4.3.1)
Output 2 type
a
(section 4.4)
Output 3 type
(section 4.5)
Output 3
activation
(section 4.5)
NSB value
(section 5.6)
Output 1
min. opening
(section 4.3.2)
Maximum
setpoint
(section 4.6)
Minimum
setpoint
(section 4.6)
0
Internal sensor
0 Cool / 0-10V 0 Not used 0 Not used 0 100% 11°C (2°F) 0 0%
Can be set
between 35°C
(95°F) and
’’minimum
setpoint + 1’’
Default value
is 35°C (95°F)
Can be set
between 10°C
(50°F) and
’’maximum
setpoint - 1’’
Default value
is 10°C (50°F)
1 Room 1 Heat / 0-10 V 1 SSR 24 VAC 1 SSR 24 VAC 1 10% 2 2°C (4°F) 1 10%
2 Return 2
Cool / 2-10 V 2 N.C. Valve 2 N.C. Valve 2 20% 3 3°C (6°F) 2 20%
3 Supply 3 Heat / 2-10 V 3 N.O. Valve 3 N.O. Valve 3 30% 4 4°C (8°F) 3 30%
4 Auto changeover 4 Mech. relay 4 Mech. relay 4 40% 5 5°C (10°F) 4 40%
5 Limited cooling 5 SSR 3-32 V 5 Contact 5 50% 6 6°C (12°F) 5 50%
6 SCR 0-10 V 6 60% 7 7°C (14°F)
7 Act. 0-10 V 7 70% 8 8°C (16°F)
8 Act. / 2-10 V 8 80% 9 9°C (18°F)
9 90%
a. If Output 2 type is set to 0-4, set the SW6 switch to Triac. If the output type is set to 5-8, set the switch to Analog (see section 4.7).
1F2T model
Application
(section 4.2)
Default mode
(section 4.3.1)
Output 2 type
a
(section 4.4)
Output 3 type
(section 4.5)
Output 3
activation
(section 4.5)
NSB value
(section 5.6)
Output 1
min. opening
(section 4.3.2)
Output 1
opening time
(section 4.3.3)
Maximum
setpoint
(section 4.6)
Minimum
setpoint
(section 4.6)
0
Internal sensor
0 Cool 0 Not used 0 Not used 0 100% 11°C (2°F) 0 0% 080
Can be set
between
35°C (95°F)
and ’’min
setpoint + 1’’
Default
value is
35°C (95°F)
Can be set
between
10°C (50°F)
and ’’max
setpoint - 1’’
Default
value is
10°C (50°F)
1 Room 1 Heat 1 SSR 24 VAC 1 SSR 24 VAC 1 10% 2 2°C (4°F) 1 10% 1 90
2 Return 2 N.C. Valve 2 N.C. Valve 2 20% 3
3°C (6°F) 2 20% 2 100
3 Supply 3 N.O. Valve 3 N.O. Valve 3 30% 4 4°C (8°F) 3 30% 3 110
4 Auto changeover 4 Mech. relay 4 Mech. relay 4 40% 5 5°C (10°F) 4 40% 4 120
5 Limited cooling 5 SSR 3-32 V 5 Contact 5 50% 6 6°C (12°F) 5 50% 5 130
6 SCR 0-10 V 6 60% 7 7°C (14°F) 6 140
7 Act. 0-10 V 7 70% 8 8°C (16°F) 7 150
8 Act. / 2-10 V 8 80% 9 9°C (18°F) 8 160
9 90%
a. If Output 2 type is set to 0-4, set the SW6 switch to Triac. If the output type is set to 5-8, set the switch to Analog (see section 4.7).
n Remove the thermostat from its base and
set the SW2 switch to MENU.
o Reinstall the thermostat. The thermostat is
now in configuration mode. The first digit
flashes to indicate that the first item of the
menu can now be modified.
p To modify the setting, use the up/down
arrows. Refer to the adjacent tables.
q Press Override to save the new setting and
go to the next item.
r Repeat steps 3 and 4 for remaining items.
s When the configuration is done, set the
SW2 switch back to NORMAL.
NOTE: Factory settings are
inside the shaded cells.